Ideal for various standard metering projects, this multifunction power meter with energy class 0.5 harmonics up to 31st provides real-time, true-RMS measurements of current, power, voltage, energy, and many other parameters. In addition, it has a 5 A/1 A current input (selectable), a 20 to 60 V DC power supply, and a standard mount.
Ideal for various standard metering projects, this multifunction power meter with energy class 0.5 harmonics up to 31st provides real-time, true-RMS measurements of current, power, voltage, energy, and many other parameters. In addition, it has a 5 A/1 A current input (selectable), a 20 to 60 V DC power supply, and a standard mount.
Le compteur d'énergie/puissance multifonction Acuvim-CL pour une ou trois phases peut être utilisé comme dispositif de collecte de données dans un système de distribution électrique intelligent. Toutes les données de surveillance sont disponibles via un port de communication numérique RS485 utilisant le protocole Modbus. Disponible avec écran LCD ou en version transducteur pour rail DIN (sans affichage).
L’Acuvim-CL utilise le protocole Modbus RTU standard de l’industrie.
Les compteurs d’énergie multifonction de la série Acuvim-L sont fabriqués par
Accuenergy. Ils constituent le choix idéal pour la surveillance et le contrôle des systèmes de distribution électrique.
L’Acuvim-L peut être utilisé comme dispositif de collecte de données dans un système de distribution électrique intelligent ou un système d'automatisation d'usine. Toutes les données de surveillance sont disponibles via un port de communication RS485 utilisant le protocole Modbus® (hors modèles Acuvim AL et BL).
La qualité du système électrique est importante en raison de l'utilisation croissante de charges électroniques telles que les ordinateurs, les ballasts ou les variateurs de fréquence. Avec l’option d’analyse de puissance de l’Acuvim-L, n’importe quel courant ou tension de phase peut être affiché et le contenu harmonique calculé. En connaissant la distribution harmonique, des actions peuvent être prises pour éviter la surchauffe des transformateurs, moteurs, condensateurs, fils neutres et les déclenchements intempestifs des disjoncteurs. Une redistribution des charges du système peut également être envisagée.
Pour les fonctions d’Heures Pleines/Heures Creuses (HP/HC), veuillez consulter le Acuvim-EL.
Mesures
Surveillance
Alarmes
Deux (2) paramètres peuvent être définis sur un intervalle de temps spécifique. Si un paramètre dépasse ou descend en dessous de la limite définie et que cela persiste durant cet intervalle, l'événement sera enregistré avec horodatage et déclenchera la sortie d’alarme DO. Le paramètre peut être choisi parmi 35 disponibles.
Communication
RS485, protocole standard Modbus® RTU ; (modèles CL/DL/EL/KL uniquement)
Option second RS485, protocole Modbus® RTU ; ou PROFIBUS-DP/V0 (disponible pour les modèles DL/EL)
Affichage
Affichage ACL clair avec rétroéclairage blanc ;
Résistance étendue aux températures environnementales.
Avec la nécessité croissante de mieux comprendre la consommation d’énergie, Accuenergy propose un logiciel simple et efficace pour compléter ses compteurs. Combiné aux compteurs, la suite logicielle Acuview offre une solution de surveillance et de mesure puissante et économique.
La série Acuvim II est disponible avec deux options de montage :
Le modèle standard est conforme à la norme ANSI C39.1 avec un format compact 96x96.
Les unités compatibles DIN respectent la norme DIN 43700. La série Acuvim L propose également un écran ACL distant en option.
Current Inputs (Each Channel) | Nominal current options: 1: 5 A 2: 1 A 3: 1 A (333 mV) 4: 1 A (100 mV Rope CT) Metering range: 1: 0 to 10 A 2: 0 to 2 A 3: 0 to 1.2 A 4: 0 to 1.2 A Pickup current: 1: 5 mA 2: 1 mA 3: 5 mA 4: 5 mA Withstand: 20 Arms continuous, 0.1% of nominal 100 Arms for 1 second, non-recurring Burden: 0.05 V A (typical) at 5 A RMS Accuracy: 0.1% at reading |
Voltage Inputs (Each Channel) | Nominal full scale: 400 V AC L-N, 690 V AC L-L (+20%) Withstand: 1500 V AC continuous; 2500 V AC, 50/60 Hz for 1 minute Input impedance: 2 MΩ per phase Metering frequency: 45 to 65 Hz, 300 to 500 Hz Pickup voltage: 10 V AC Accuracy: 0.1% at reading |
Energy Accuracy | Active: Class 0.5s (IEC 62053-22), Class 0.5s (ANSI C12.20) Reactive: Class 0.5 (IEC62053-24) |
Harmonic Resolution | Metered value: 2nd to 31st Harmonic (50 or 60 Hz type) |
Communications | Modbus-RTU or BACnet MS/TP: Modbus-RTU 2-wire shielded twisted pair cable connection 1200 to 115,200 bps |
Control Power | Universal: AC or DC Operating Range: 100 to 415 V AC, 50/60 Hz; 100 to 300 V DC Burden: 5 W Frequency: 50/60 Hz Withstand: 3250 V AC, 50/60 Hz for 1 minute Installation Category III (Distribution) |
Power | Supply: 100 to 415 V AC, 50/60 Hz, 100 to 300 V DC Consumption: 3 W |
Environmental Conditions | Operating temperature: -13 to 158°F (-25 to 70°C) Storage temperature: -40 to 176°F (-40 to 85°C) Relative humidity: 5 to 95% non-condensing |
Protection Level | IP56 (front), IP30 (cover) |
Standard Compliance and Certifications | Measurement standard: IEC 62053-22, ANSI C12.20, IEC61557-12 Environmental standard: IEC 60068-2, CE, RoHS Safety standard: IEC 61010-1, UL 61010-1 EMC standard: IEC 61000-4/-2-3-4-5-6-8-11, CISPR 22, IEC 61000-3-2, IEC 61000-6-2/4 Outlines standard: DIN 43700, ANSI C39.1 Protocol conformance: IEC 61850 2nd Edition |
Dimensions | 3.8 x 3.8 x 2" (96 x 96 x 50.7 mm) Cut-out: 3.62 x 3.62" (92 x 92 mm) or 4" (102 mm) round |
Weight | 0.77 lbs (350 g) |
Cliquer sur une catégorie pour voir une sélection d'accessoires compatible avec le Accuenergy Acuvim-CL Series Multifunction Power and Energy Meter with panel mounting with display, 5 A/1 A input, 20 to 60 V DC.
Current Inputs (Each Channel) | Nominal current options: 1: 5 A 2: 1 A 3: 1 A (333 mV) 4: 1 A (100 mV Rope CT) Metering range: 1: 0 to 10 A 2: 0 to 2 A 3: 0 to 1.2 A 4: 0 to 1.2 A Pickup current: 1: 5 mA 2: 1 mA 3: 5 mA 4: 5 mA Withstand: 20 Arms continuous, 0.1% of nominal 100 Arms for 1 second, non-recurring Burden: 0.05 V A (typical) at 5 A RMS Accuracy: 0.1% at reading |
Voltage Inputs (Each Channel) | Nominal full scale: 400 V AC L-N, 690 V AC L-L (+20%) Withstand: 1500 V AC continuous; 2500 V AC, 50/60 Hz for 1 minute Input impedance: 2 MΩ per phase Metering frequency: 45 to 65 Hz, 300 to 500 Hz Pickup voltage: 10 V AC Accuracy: 0.1% at reading |
Energy Accuracy | Active: Class 0.5s (IEC 62053-22), Class 0.5s (ANSI C12.20) Reactive: Class 0.5 (IEC62053-24) |
Harmonic Resolution | Metered value: 2nd to 31st Harmonic (50 or 60 Hz type) |
Communications | Modbus-RTU or BACnet MS/TP: Modbus-RTU 2-wire shielded twisted pair cable connection 1200 to 115,200 bps |
Control Power | Universal: AC or DC Operating Range: 100 to 415 V AC, 50/60 Hz; 100 to 300 V DC Burden: 5 W Frequency: 50/60 Hz Withstand: 3250 V AC, 50/60 Hz for 1 minute Installation Category III (Distribution) |
Power | Supply: 100 to 415 V AC, 50/60 Hz, 100 to 300 V DC Consumption: 3 W |
Environmental Conditions | Operating temperature: -13 to 158°F (-25 to 70°C) Storage temperature: -40 to 176°F (-40 to 85°C) Relative humidity: 5 to 95% non-condensing |
Protection Level | IP56 (front), IP30 (cover) |
Standard Compliance and Certifications | Measurement standard: IEC 62053-22, ANSI C12.20, IEC61557-12 Environmental standard: IEC 60068-2, CE, RoHS Safety standard: IEC 61010-1, UL 61010-1 EMC standard: IEC 61000-4/-2-3-4-5-6-8-11, CISPR 22, IEC 61000-3-2, IEC 61000-6-2/4 Outlines standard: DIN 43700, ANSI C39.1 Protocol conformance: IEC 61850 2nd Edition |
Dimensions | 3.8 x 3.8 x 2" (96 x 96 x 50.7 mm) Cut-out: 3.62 x 3.62" (92 x 92 mm) or 4" (102 mm) round |
Weight | 0.77 lbs (350 g) |
Cliquer sur une catégorie pour voir une sélection d'accessoires compatible avec le Accuenergy Acuvim-CL Series Multifunction Power and Energy Meter with panel mounting with display, 5 A/1 A input, 20 to 60 V DC.