5 kV DC DielectricTest Set; 2.5 & 5 kV; 5 mA.
5 kV DC DielectricTest Set; 2.5 & 5 kV; 5 mA.
Dielectric test sets measure leakage current while applying a dc voltage at or above the insulation system's operating level. This measurement aids in determining the insulation system's ability to withstand overvoltages such as lightning strikes and switching surges.
Megger portable dc dielectric test sets check the electrical
insulation quality of motors, power cables, switchgear, insulators, transformers and capacitors. Typical applications include acceptance and maintenance testing of critical equipment
used by electrical utility substations and industrial plant distribution systems. Power apparatus manufacturers may also use
the equipment to perform QA/QC production tests.
The test sets can be used to perform step-voltage and proof
tests which, when incorporated into a routine maintenance
program, can aid in predicting potential failure before breakdown occurs.
Megger's 220005, a 5-kV unit for testing equipment is rated for 2.5 kV and below, and is suitable for testing
power cable, switchgear and rotating machinery in accordance with IEEE, ICEA, NEMA and ANSI guidelines.
Because Megger dc dielectric test sets act like full-wave rectified units, they also are suitable for applications involving
vacuum bottles.
Direct current high-potential testing provides several advantages over alternating current. Direct current test equipment uses far less power, provides fast charging of highly capacitive test samples, can be easily transported to the test site and costs less. Additionally, the dc test can detect incipient breakdown without the possibility of damage to good insulation.
Input | 120 Vac, 50/60 Hz |
Output | Voltage: 0 to 15 kVdc, negative with respect to ground Current: 2 mA continuous Short Circuit: 12 mA max., limited by circuit breaker |
Metering | Kilovoltmeter: 4-in. (102-mm) taut band with two ranges, 0 to 7.5 and 0 to 15.0 kV Current Meter: 4-in. (102-mm) taut band with four ranges, 0 to 5/50/500 µA and 5 mA |
Accuracy | ±2% of full scale |
Temperature Range | 0 to 122° F (-17.7 to +50° C) operating |
Cliquer sur une catégorie pour voir une sélection d'accessoires compatible avec le Megger 220005 5kV DC DielectricTest Set.
Input | 120 Vac, 50/60 Hz |
Output | Voltage: 0 to 15 kVdc, negative with respect to ground Current: 2 mA continuous Short Circuit: 12 mA max., limited by circuit breaker |
Metering | Kilovoltmeter: 4-in. (102-mm) taut band with two ranges, 0 to 7.5 and 0 to 15.0 kV Current Meter: 4-in. (102-mm) taut band with four ranges, 0 to 5/50/500 µA and 5 mA |
Accuracy | ±2% of full scale |
Temperature Range | 0 to 122° F (-17.7 to +50° C) operating |
Cliquer sur une catégorie pour voir une sélection d'accessoires compatible avec le Megger 220005 5kV DC DielectricTest Set.