Veris HS1NX Replaceable Humidity Element, 1%

Modèle: HS1NX

Veris HS1NX Replaceable Humidity Element, 1%

Modèle: HS1NX

The humidity monitoring replaceable element is designed to reduce downtime.

The humidity monitoring replaceable element is designed to reduce downtime.

Prix spécial $190.95 CAD
Prix régulier $397.70 CAD
Disponibilité 2 à 3 semaines
Quantité

Spécifications pour le Veris HS1NX

HS Element Digitally profiled thin-film capacitive (32-bit mathematics) U.S. Patent 5,844,138
Accuracy ±1%, 2%, 3% or 5% (specify) at 10 to 80% RH (multi-point calibration, NIST traceable) at 77°F (25°C)
Reset Rate 24 hours
Stability ±1% at 68°F (20°C) annually, for 2 years
Operating Humidity Range 0 to 100% RH (non-condensing)
Temperature Coefficient ±0.1% RH/°C above or below 77°F (25°C) (typically)
Analog Output 4 to 20 mA mode: 2-wire, polarity insensitive (clipped and capped); 0 to 5 V/0 to 10 V mode: 3-wire, observe polarity
Scaling 0 to 100% RH
Operating Temperature Range -58 to 122°F (-50 to 50°C)
Input Power 4 to 20 mA mode: loop powered 12 to 30 VDC only, 30 mA max.; 0 to 5 V/0 to 10 V mode: 12 to 30 VDC/24 VAC, 15 mA max
Temperature Transmitter Output Digital, 4 to 20 mA (clipped and capped) or 0 to 5 V/0 to 10 V output; accuracy ±1°F (±0.5°C) typical
Range 50 to 95°F (10 to 35°C)

Le Veris HS1NX comprend

  • Veris HS1NX Replaceable Humidity Element, 1%

Poser une question sur le Veris HS1NX Replaceable Humidity Element, 1%

Spécifications pour le Veris HS1NX

HS Element Digitally profiled thin-film capacitive (32-bit mathematics) U.S. Patent 5,844,138
Accuracy ±1%, 2%, 3% or 5% (specify) at 10 to 80% RH (multi-point calibration, NIST traceable) at 77°F (25°C)
Reset Rate 24 hours
Stability ±1% at 68°F (20°C) annually, for 2 years
Operating Humidity Range 0 to 100% RH (non-condensing)
Temperature Coefficient ±0.1% RH/°C above or below 77°F (25°C) (typically)
Analog Output 4 to 20 mA mode: 2-wire, polarity insensitive (clipped and capped); 0 to 5 V/0 to 10 V mode: 3-wire, observe polarity
Scaling 0 to 100% RH
Operating Temperature Range -58 to 122°F (-50 to 50°C)
Input Power 4 to 20 mA mode: loop powered 12 to 30 VDC only, 30 mA max.; 0 to 5 V/0 to 10 V mode: 12 to 30 VDC/24 VAC, 15 mA max
Temperature Transmitter Output Digital, 4 to 20 mA (clipped and capped) or 0 to 5 V/0 to 10 V output; accuracy ±1°F (±0.5°C) typical
Range 50 to 95°F (10 to 35°C)