The humidity monitoring deluxe duct sensor provides an ideal solution for measuring the relative humidity in all conditions.
The humidity monitoring deluxe duct sensor provides an ideal solution for measuring the relative humidity in all conditions.
Discontinué!
Ce produit a été discontinué et n’est plus disponible.
Voici le produit de remplacement direct :
The humidity monitoring deluxe duct sensor provides an ideal solution for measuring the relative humidity in all conditions.
Caractéristiques
Applications
| HS Element | Digitally profiled thin-film capacitive (32-bit mathematics) U.S. Patent 5,844,138 |
| Accuracy | ±1%; (multi-point calibration, NIST traceable) at 77°F (25°C) from 10 to 80% RH |
| Reset Rate | 24 hours |
| Stability | ±1% at 68°F (20°C) annually, for 2 years |
| Operating Humidity Range | 0 to 100% RH (non-condensing) |
| Hysteresis | 1.5% typical |
| Temperature Effect | ±0.1% RH/°C above or below 77°F (25°C) (typical) |
| Analog Output | 4 to 20 mA mode: 2-wire, polarity insensitive (clipped and capped) |
| Scaling | 0 to 100% RH |
| Operating Temperature Range | -40 to 122°F (-40 to 50°C) |
| Input Power | Loop powered 12 to 30 VDC only, 30 mA max |
| Temperature Transmitter Output | Digital, 4 to 20 mA (clipped and capped) or 0 to 5 V/0 to 10 V output; accuracy ±1°F (±0.5°C) typical |
| HS Element | Digitally profiled thin-film capacitive (32-bit mathematics) U.S. Patent 5,844,138 |
| Accuracy | ±1%; (multi-point calibration, NIST traceable) at 77°F (25°C) from 10 to 80% RH |
| Reset Rate | 24 hours |
| Stability | ±1% at 68°F (20°C) annually, for 2 years |
| Operating Humidity Range | 0 to 100% RH (non-condensing) |
| Hysteresis | 1.5% typical |
| Temperature Effect | ±0.1% RH/°C above or below 77°F (25°C) (typical) |
| Analog Output | 4 to 20 mA mode: 2-wire, polarity insensitive (clipped and capped) |
| Scaling | 0 to 100% RH |
| Operating Temperature Range | -40 to 122°F (-40 to 50°C) |
| Input Power | Loop powered 12 to 30 VDC only, 30 mA max |
| Temperature Transmitter Output | Digital, 4 to 20 mA (clipped and capped) or 0 to 5 V/0 to 10 V output; accuracy ±1°F (±0.5°C) typical |