Features a small external diameter and is made of 316L stainless steel, the hydrostatic level transmitter is designed for measuring levels in water wells and drinking water tanks. It is an accurate 2-wire transmitter with a piezoresistive measuring system with direct air pressure and temperature compensation.
Features a small external diameter and is made of 316L stainless steel, the hydrostatic level transmitter is designed for measuring levels in water wells and drinking water tanks. It is an accurate 2-wire transmitter with a piezoresistive measuring system with direct air pressure and temperature compensation.
The hydrostatic level transmitter is submersible.
Features
Applications
| Nominal Measuring Range | 0 to 30' |
| Measuring Principle | Piezoresistive (pressure) |
| Min. Programmable Range | 0 to 12' |
| Max. Programmable Range | 0 to 36' |
| Non-Standard Range | Min. 0 to 6'. / Max. 0 to 900' |
| Max. Overpressure | 3.5 bar/50 psi |
| Temperature Range | -15 to 150°F |
| Temp. Deviation, Zero Point | Better than ± 0.01 % /°F |
| Temperature Deviation, Full Range | Better than ± 0.008 % /°F |
| Linearity/Stability | Better than ± 0.5 % FS / ± 0.1 % FS |
| Measurement Accuracy | Better than ± 0.25 % FS @ 50 to 85°F Better than ± 0.5 % FS @ full temperature range |
| Long Time Stability | Better than ± 0.5 % FS per year |
| Materials | Housing and diaphragm made from stainless steel (AISI 316 L) |
| Supply Voltage | 10 to 30 V DC |
| Output Signal | 2-wire 4 to 20 mA (passive transmitter) |
| Cable | 2 × AWG 20 (pressure) + 5 x AWG 25 (data), shielded, PUR insulation |
| Cable Length | 39' |
| Enclosure | NEMA 6P, withstands a static pressure equal to max. overpressure |
| Test Approvals | EN61000-6-3/-4:2001, EN61000-6-1/-2:1999 |
| Nominal Measuring Range | 0 to 30' |
| Measuring Principle | Piezoresistive (pressure) |
| Min. Programmable Range | 0 to 12' |
| Max. Programmable Range | 0 to 36' |
| Non-Standard Range | Min. 0 to 6'. / Max. 0 to 900' |
| Max. Overpressure | 3.5 bar/50 psi |
| Temperature Range | -15 to 150°F |
| Temp. Deviation, Zero Point | Better than ± 0.01 % /°F |
| Temperature Deviation, Full Range | Better than ± 0.008 % /°F |
| Linearity/Stability | Better than ± 0.5 % FS / ± 0.1 % FS |
| Measurement Accuracy | Better than ± 0.25 % FS @ 50 to 85°F Better than ± 0.5 % FS @ full temperature range |
| Long Time Stability | Better than ± 0.5 % FS per year |
| Materials | Housing and diaphragm made from stainless steel (AISI 316 L) |
| Supply Voltage | 10 to 30 V DC |
| Output Signal | 2-wire 4 to 20 mA (passive transmitter) |
| Cable | 2 × AWG 20 (pressure) + 5 x AWG 25 (data), shielded, PUR insulation |
| Cable Length | 39' |
| Enclosure | NEMA 6P, withstands a static pressure equal to max. overpressure |
| Test Approvals | EN61000-6-3/-4:2001, EN61000-6-1/-2:1999 |