Digital clamp meter with tear drop shaped, medium size transformer jaws specially designed for leakage current measurement. Also features a frequency filter switch to eliminate the effect of harmonics.
Digital clamp meter with tear drop shaped, medium size transformer jaws specially designed for leakage current measurement. Also features a frequency filter switch to eliminate the effect of harmonics.
Discontinué!
Ce produit a été discontinué et n’est plus disponible. Il n'y a aucune option de remplacement.
Nous pouvons vous aider à trouver ce dont vous avez besoin:
Features
AC A (50/60Hz) | |
Ranges | 20mA 200mA 2A 20A 200A 500A |
Accuracy | 20/200mA/2A: ±1.5%rdg ±5dgt 20/200A: ±2%rdg ±5dgt 500A: ±2.5%rdg ±5dgt |
AC A (WIDE) | |
Ranges | 200mA 2A 20A 200A 1000A |
Accuracy | 20/200mA/2A 50/60Hz: ±1%rdg ±3dgt 40 to 400Hz: ±5%rdg ±5dgt 20/200A 50/60Hz: ±1.5%rdg ±3dgt 40 to 400Hz: ±5%rdg ±5dgt 500A 50/60Hz: ±2%rdg ±3dgt 40 to 400Hz: ±5%rdg ±5dgt |
AC V | |
Accuracy | 600V 50/60Hz: ±2%rdg ±5dgt 40 to 400Hz: ±5%rdg ±5dgt |
Resistance | |
Accuracy | 200Ω: ±1.5%rdg ±5dgt |
General Specifications | |
Conductor Size | Ø40mm max. |
Effect of External Stray Magnetic Field: Ø15mm 100A | 10mA AC max. |
Frequency Response | 40 to 400Hz |
Dimensions | 209 x 96 x 45 mm |
Weight | Approx. 450 g |
AC A (50/60Hz) | |
Ranges | 20mA 200mA 2A 20A 200A 500A |
Accuracy | 20/200mA/2A: ±1.5%rdg ±5dgt 20/200A: ±2%rdg ±5dgt 500A: ±2.5%rdg ±5dgt |
AC A (WIDE) | |
Ranges | 200mA 2A 20A 200A 1000A |
Accuracy | 20/200mA/2A 50/60Hz: ±1%rdg ±3dgt 40 to 400Hz: ±5%rdg ±5dgt 20/200A 50/60Hz: ±1.5%rdg ±3dgt 40 to 400Hz: ±5%rdg ±5dgt 500A 50/60Hz: ±2%rdg ±3dgt 40 to 400Hz: ±5%rdg ±5dgt |
AC V | |
Accuracy | 600V 50/60Hz: ±2%rdg ±5dgt 40 to 400Hz: ±5%rdg ±5dgt |
Resistance | |
Accuracy | 200Ω: ±1.5%rdg ±5dgt |
General Specifications | |
Conductor Size | Ø40mm max. |
Effect of External Stray Magnetic Field: Ø15mm 100A | 10mA AC max. |
Frequency Response | 40 to 400Hz |
Dimensions | 209 x 96 x 45 mm |
Weight | Approx. 450 g |