This power quality analyzer set comes with one 3-phase and 1 single-phase flexible current transformer that have a 30/300/3,000Arms measuring range and a 24in (60.96cm) length.
This power quality analyzer set comes with one 3-phase and 1 single-phase flexible current transformer that have a 30/300/3,000Arms measuring range and a 24in (60.96cm) length.
Discontinué!
Ce produit a été discontinué et n’est plus disponible.
Il n’y a pas de remplacement direct, mais nous vous recommandons:
Vous ne trouvez pas ce que vous cherchez? Nous ferons une recherche et vous aiderons à trouver ce dont vous avez besoin.
The HDPQ® Xplorer SP combines state-of-the-art power monitoring with high-speed transient capture (1 microsecond/channel) and "best-in-class" communication capabilities to provide users with a revolutionary monitoring experience.
Features
Applications
| Measured Parameters | |
| Differential Voltage Inputs (4) | 1 to 1000Vrms, AC/DC; ±0.1% rdg., <40V ±0.05% FS; 512 samples/cycle; 16-bit ADC resolution | 
| Current Inputs with CTs (4) | 30/300/3000Arms AC; ±0.1% rdg. ±0.05% FS; 512 samples/cycle; 16-bit ADC resolution | 
| Frequency Range | 42.5 to 69Hz, ±0.01Hz, 380 to 420Hz ±0.1Hz | 
| Calculated Parameters | |
| Vthd | 0 to 100%, ±5% for V ≥ 1% Vnom | 
| V Ind Harm | DC, 2 to 127, ±5% for V ≥ 1% Vnom | 
| Ithd | 0 to 100%, ±5% for V ≥ 1% Vnom | 
| I Ind Harm | DC, 2 to 63, ±5% for V ≥ 1% Vnom | 
| Pst | 10 minutes: 0.2 to 10, ±0.05 at Pst=1 | 
| Plt | 2 hours: 0.2 to 10, ±0.05 at Pst=1 | 
| General Specifications | |
| Memory Size | 4GB | 
| Power Supply | 90 to 600VAC/500VDC (50/60Hz); powered by the phase being measured or other source | 
| Dimensions | 11 x 2.5 x 6.5in (27.9 x 6.4 x 16.5cm) | 
| Weight | 3.8lbs (1.7kg) | 
| Measured Parameters | |
| Differential Voltage Inputs (4) | 1 to 1000Vrms, AC/DC; ±0.1% rdg., <40V ±0.05% FS; 512 samples/cycle; 16-bit ADC resolution | 
| Current Inputs with CTs (4) | 30/300/3000Arms AC; ±0.1% rdg. ±0.05% FS; 512 samples/cycle; 16-bit ADC resolution | 
| Frequency Range | 42.5 to 69Hz, ±0.01Hz, 380 to 420Hz ±0.1Hz | 
| Calculated Parameters | |
| Vthd | 0 to 100%, ±5% for V ≥ 1% Vnom | 
| V Ind Harm | DC, 2 to 127, ±5% for V ≥ 1% Vnom | 
| Ithd | 0 to 100%, ±5% for V ≥ 1% Vnom | 
| I Ind Harm | DC, 2 to 63, ±5% for V ≥ 1% Vnom | 
| Pst | 10 minutes: 0.2 to 10, ±0.05 at Pst=1 | 
| Plt | 2 hours: 0.2 to 10, ±0.05 at Pst=1 | 
| General Specifications | |
| Memory Size | 4GB | 
| Power Supply | 90 to 600VAC/500VDC (50/60Hz); powered by the phase being measured or other source | 
| Dimensions | 11 x 2.5 x 6.5in (27.9 x 6.4 x 16.5cm) | 
| Weight | 3.8lbs (1.7kg) |