This power quality analyzer set comes with 4 TR-2550B clamp-on current transformers that have a 1 to 100Arms measuring range and a 15mm diameter maximum conductor size.
This power quality analyzer set comes with 4 TR-2550B clamp-on current transformers that have a 1 to 100Arms measuring range and a 15mm diameter maximum conductor size.
Discontinué!
Ce produit a été discontinué et n’est plus disponible. Il n’y a pas de produit de remplacement direct. Ne vous inquiétez pas, nous avons quelques options pour vous aider à trouver ce dont vous avez besoin:
Visitez notre catégorie Compteurs à panneau pour trouver des produits similaires.
Ou nous ferons une recherche et vous aiderons à trouver ce dont vous avez besoin:
The HDPQ Visa SP series of power quality analyzers offers the best value in power quality, demand and energy monitoring from Dranetz.
Features
Applications
Measured Parameters | |
Differential Voltage Inputs (4) | 1 to 1000Vrms, AC/DC; ±0.1% rdg., <40V ±0.05% FS; 512 samples/cycle; 16-bit ADC resolution |
Current Inputs with CTs (4) | 1 to 100Arms AC; ±0.1% rdg. ±0.05% FS; 512 samples/cycle; 16-bit ADC resolution |
Frequency Range | 16 to 25Hz, 42.5 to 69Hz, ±0.01Hz |
Calculated Parameters | |
Vthd | 0 to 100%, ±5% for V ≥ 1% Vnom |
V Ind Harm | DC, 2 to 127, ±5% for V ≥ 1% Vnom |
Ithd | 0 to 100%, ±5% for V ≥ 1% Vnom |
I Ind Harm | DC, 2 to 63, ±5% for V ≥ 1% Vnom |
Pst | 10 minutes: 0.2 to 10, ±0.05 at Pst=1 |
Plt | 2 hours: 0.2 to 10, ±0.05 at Pst=1 |
General Specifications | |
Memory Size | 4GB |
Power Supply | 90 to 600VAC/500VDC (50/60Hz); powered by the phase being measured or other source |
Dimensions | 11 x 2.5 x 6.5in (27.9 x 6.4 x 16.5cm) |
Weight | 3.8lbs (1.72kg) |
Measured Parameters | |
Differential Voltage Inputs (4) | 1 to 1000Vrms, AC/DC; ±0.1% rdg., <40V ±0.05% FS; 512 samples/cycle; 16-bit ADC resolution |
Current Inputs with CTs (4) | 1 to 100Arms AC; ±0.1% rdg. ±0.05% FS; 512 samples/cycle; 16-bit ADC resolution |
Frequency Range | 16 to 25Hz, 42.5 to 69Hz, ±0.01Hz |
Calculated Parameters | |
Vthd | 0 to 100%, ±5% for V ≥ 1% Vnom |
V Ind Harm | DC, 2 to 127, ±5% for V ≥ 1% Vnom |
Ithd | 0 to 100%, ±5% for V ≥ 1% Vnom |
I Ind Harm | DC, 2 to 63, ±5% for V ≥ 1% Vnom |
Pst | 10 minutes: 0.2 to 10, ±0.05 at Pst=1 |
Plt | 2 hours: 0.2 to 10, ±0.05 at Pst=1 |
General Specifications | |
Memory Size | 4GB |
Power Supply | 90 to 600VAC/500VDC (50/60Hz); powered by the phase being measured or other source |
Dimensions | 11 x 2.5 x 6.5in (27.9 x 6.4 x 16.5cm) |
Weight | 3.8lbs (1.72kg) |