Portable and easy to operate, this AC hipot test set features adjustable AC voltage for a pass/fail, AC over-voltage withstand test on high voltage apparatus, and output up to 3 kVa. Moreover, this hipot has a protection circuit, a three-range current meter, and a two-range voltmeter for accurate leakage current readings.
Our rentals come fully calibrated to traceable standards. Have your own instrument? We also offer calibration services for this model (CERTIHP2).
Portable and easy to operate, this AC hipot test set features adjustable AC voltage for a pass/fail, AC over-voltage withstand test on high voltage apparatus, and output up to 3 kVa. Moreover, this hipot has a protection circuit, a three-range current meter, and a two-range voltmeter for accurate leakage current readings.
Our rentals come fully calibrated to traceable standards. Have your own instrument? We also offer calibration services for this model (CERTIHP2).
This product exceeds standard shipping dimensions/weight, as such it does not qualify for free shipping. We will contact you with your shipping costs.
These hipots are designed for conducting pass/fail, AC over-voltage withstand tests on high voltage equipment such as switchgear, circuit breakers, reclosers, vacuum bottles, hot sticks, bus duct, and other apparatus that require an AC test voltage. The PFT Series offers the most convenient and affordable field portable AC hipots available at this voltage and power range.
The hipots feature a gapped core transformer that can provide up to 3 kVA of output power while drawing only 1.5 kVA, allowing the hipot to be powered by a standard 120Vac or 230Vac input. They are equipped with a two-range voltmeter, three-range current meter, and guard circuit to ensure precise leakage current measurements. For bench-top testing requirements, we recommend checking out our ABT Series. If you need higher power options, our ALT, FPA, HPA, and PAR lines of AC dielectric test sets can accommodate testing loads that require more power.
Features
Input | 120 V, 60 Hz, 15 A |
Output | 0 to 50 kV AC, 1 kVA resistive load 3 kVA capacitive load, up to 60 mA current Output current is reduced at lower voltages |
Duty | 3 kVA: ½ hour ON, 2 hours OFF 2 kVA: 1 hour ON, 1 hour OFF 1 kVA: continuous |
Voltmeter | 3.5" (135 cm) scaled 0-25/50 kV AC, ±2% F.S. |
Current Meter | 3.5" (135 cm), scaled 0-1 mA, ±2% F.S. with range multipliers of x1, x10, x100 |
Distortion | Less than 5% |
Output Termination | 20' (6 m) shielded output cable with alligator clamp |
Scope of Supply | 20' (6 m) black ground lead, 20' (6 m) shielded return cable, external interlock plug, operations manual, calibration certificate |
Dimension | 21 x 11.25 x 15.25" (534 x 286 x 387 mm) |
Weight | 75 lbs (34 kg) |
Input | 120 V, 60 Hz, 15 A |
Output | 0 to 50 kV AC, 1 kVA resistive load 3 kVA capacitive load, up to 60 mA current Output current is reduced at lower voltages |
Duty | 3 kVA: ½ hour ON, 2 hours OFF 2 kVA: 1 hour ON, 1 hour OFF 1 kVA: continuous |
Voltmeter | 3.5" (135 cm) scaled 0-25/50 kV AC, ±2% F.S. |
Current Meter | 3.5" (135 cm), scaled 0-1 mA, ±2% F.S. with range multipliers of x1, x10, x100 |
Distortion | Less than 5% |
Output Termination | 20' (6 m) shielded output cable with alligator clamp |
Scope of Supply | 20' (6 m) black ground lead, 20' (6 m) shielded return cable, external interlock plug, operations manual, calibration certificate |
Dimension | 21 x 11.25 x 15.25" (534 x 286 x 387 mm) |
Weight | 75 lbs (34 kg) |