Networked electrical submetering provides meaningful energy data that is used to accurately allocate energy costs, identify energy cost-savings opportunities, and lower utility bills. The flexible design of the PowerScout 48 HD allows it to be configured for monitoring any combination of up to 16 three-phase or 48 single-phase electrical circuits across two separate voltages with revenue grade accuracy (ANSI C12.20-2010 Class 0.2). DENTCloud submetering data analytics platform provides secure, subscription-free, real-time access to your energy data anywhere in the world. Equip the PowerScout 48 HD meter with any combination of DENT’s split-core, solid-core, or RoCoil (Rogowski) CTs. Comes with a UL 94-V0 enclosure and display.
Networked electrical submetering provides meaningful energy data that is used to accurately allocate energy costs, identify energy cost-savings opportunities, and lower utility bills. The flexible design of the PowerScout 48 HD allows it to be configured for monitoring any combination of up to 16 three-phase or 48 single-phase electrical circuits across two separate voltages with revenue grade accuracy (ANSI C12.20-2010 Class 0.2). DENTCloud submetering data analytics platform provides secure, subscription-free, real-time access to your energy data anywhere in the world. Equip the PowerScout 48 HD meter with any combination of DENT’s split-core, solid-core, or RoCoil (Rogowski) CTs. Comes with a UL 94-V0 enclosure and display.
Maximum flexibility for monitoring
The PowerScout 48 HD is a versatile, multi-channel instrument with a flexible design that enables configuration for monitoring multiple electrical circuits. Monitor any combination of up to 16 three-phase or 48 single-phase electrical devices with a single PowerScout HD. With data updates every 1 second and ANSI C12.20-2010 Class 0.2 revenue-grade accuracy (depending on CT), the PowerScout 48 HD is ideal for data center monitoring, tenant submetering, and accountability metering in commercial, retail, and industrial facilities.
Industry-standard modbus or bacnet
The PowerScout 48 HD supports both Modbus and BACnet communication protocols that are field selectable and interfaces are available through standard serial RS-485 or Ethernet. Unique to the PowerScout 48 HD are two independent dry-contact pulse inputs, allowing for monitoring of customer-derived voltage networks. Configure each of the input channels independently with customizable units of measure (i.e., gallons) within ViewPoint HD software.
Interval data recording and RTC
The PowerScout HD Series features interval data recording of kWh. The meter’s non-volatile memory stores up to 63 days of 15-minute kWh data that can be downloaded in the event of lost communication with the RTU. The CSV data file can be quickly downloaded through a direct USB or Ethernet connection using ViewPoint HD software and can be used to backfill any missing data. This feature works automatically in the background to record data - no configuration necessary. In addition, the PowerScout HD Series has a capacitor-backed real-time clock (RTC) to ensure an accurate time stamp on all recorded data records. Unlike other systems, there is no battery to change and the capacitor retains calendar time for up to 1 week. The clock can be synchronized with the PC clock during meter setup.
Easy installation
Every PowerScout is line-powered and designed to operate on any voltage from 90 to 600 V AC. Configure the meter prior to installation using the ViewPoint HD software utility with a direct USB connection or via the built-in web server. Any combination of split-core or flexible RōCoil CTs can be used, however, for Legal Tenant Billing Applications in California, meters and CTs must receive CTEP approval. Patented PhaseChek™ technology ensures proper CT-to-phase installation the first time, eliminating costly return trips to the field.
Features
Applications
Service Type | Single phase, split phase, three phase-four wire (WYE), three phase-three wire (delta) |
Power | From L1 phase to L2 phase. 90 to 600 V AC RMS CAT III 50/60 Hz, 500 mA AC maximum |
Power Out | Unregulated 12 V DC output, 200 mA, self-resetting fuse |
AC Protection | 0.5 A fuse 200 kA interrupt capacity |
Voltage Channels | 80 to 346 V AC line-to-neutral, 600 V line-to-line, CAT III |
Current Channels | 48 channels, 0.525 V AC maximum, 333 mV CTs, 0 to 4000+ A, depending on CT |
Maximum Current Input | 150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000 A with RōCoil CTs |
Measurement Type | True RMS using high-speed digital signal processing (DSP) with continuous sampling |
Line Frequency | 50/60 Hz |
Waveform Sampling | 1.8 kHz |
Parameter Update Rate | 1 second |
Measurements | Volts, amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, import (received) kWh, export (delivered) kWh, net kWh, import (received) kVAh, export (delivered) kVAh, net kVAh, import (received) kVARh, export (delivered) kVARh, net kVARh, THD, theta, frequency. All parameters for each phase and system total |
Accuracy | 0.2% ANSI C12.20-2010 Class 0.2 |
Resolution | Values reported in IEEE-754 single precision floating point format (32 bit) |
Display | 4-line display, tri-color backlight (PhaseChek) |
Hardware | RS-485, Ethernet, and USB (for ViewPoint HD use only) |
Supported Protocols | Modbus (using SunSpec IEEE-754 single precision floating point model), or BACnet |
Max Distance | 3937' (1200 m) with data range of 100 K bits per second or less |
Supported BAUD Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
Data Bits | 8 |
Parity | None, even, odd |
Stop Bit | 2, 1 |
Data Formats | Modbus, BACnet MS/TP, Modbus TCP or BACnet IP |
Dimensions | 13.5 x 10 x 3" (34.3 x 25.4 x 7.6 cm) |
Service Type | Single phase, split phase, three phase-four wire (WYE), three phase-three wire (delta) |
Power | From L1 phase to L2 phase. 90 to 600 V AC RMS CAT III 50/60 Hz, 500 mA AC maximum |
Power Out | Unregulated 12 V DC output, 200 mA, self-resetting fuse |
AC Protection | 0.5 A fuse 200 kA interrupt capacity |
Voltage Channels | 80 to 346 V AC line-to-neutral, 600 V line-to-line, CAT III |
Current Channels | 48 channels, 0.525 V AC maximum, 333 mV CTs, 0 to 4000+ A, depending on CT |
Maximum Current Input | 150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000 A with RōCoil CTs |
Measurement Type | True RMS using high-speed digital signal processing (DSP) with continuous sampling |
Line Frequency | 50/60 Hz |
Waveform Sampling | 1.8 kHz |
Parameter Update Rate | 1 second |
Measurements | Volts, amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, import (received) kWh, export (delivered) kWh, net kWh, import (received) kVAh, export (delivered) kVAh, net kVAh, import (received) kVARh, export (delivered) kVARh, net kVARh, THD, theta, frequency. All parameters for each phase and system total |
Accuracy | 0.2% ANSI C12.20-2010 Class 0.2 |
Resolution | Values reported in IEEE-754 single precision floating point format (32 bit) |
Display | 4-line display, tri-color backlight (PhaseChek) |
Hardware | RS-485, Ethernet, and USB (for ViewPoint HD use only) |
Supported Protocols | Modbus (using SunSpec IEEE-754 single precision floating point model), or BACnet |
Max Distance | 3937' (1200 m) with data range of 100 K bits per second or less |
Supported BAUD Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
Data Bits | 8 |
Parity | None, even, odd |
Stop Bit | 2, 1 |
Data Formats | Modbus, BACnet MS/TP, Modbus TCP or BACnet IP |
Dimensions | 13.5 x 10 x 3" (34.3 x 25.4 x 7.6 cm) |