400 Amp. AVG, 400A AC, 600V AC/DC, Continuity.
400 Amp. AVG, 400A AC, 600V AC/DC, Continuity.
Discontinué!
Ce produit a été discontinué et n’est plus disponible.
Voici le produit de remplacement direct :
| Specifications | |||||||
| Voltage DC |
|
||||||
| Range | 0 - 600.0 V | ||||||
| Accuracy | 1% ± 5 counts | ||||||
| Voltage AC |
|
||||||
| Range | 0 - 600.0 V | ||||||
| Accuracy | 1% ± 5 counts (50/60 Hz) | ||||||
| AC Response | Averaging | ||||||
| Current AC |
|
||||||
| Range | 0 - 400.0 A | ||||||
| Accuracy | 2% ± 5 counts (50/60 Hz) | ||||||
| AC Response | Averaging | ||||||
| Resistance |
|
||||||
| Range | 0 - 600.0 Ω | ||||||
| Accuracy | 1.5% ± 5 counts | ||||||
| Continuity |
|
||||||
| <= 30 Ω </td> | |||||||
| Environmental Specifications | |||||||
| Operating Temperature |
|
||||||
| -10°C to +50°C, -14°F to 122°F | |||||||
| Storage Temperature | |||||||
| -40�C to +60ºC, -22°F to 140°F | |||||||
| Operating Altitude |
|
||||||
| 2,500 meters max, 6,500 ft max | |||||||
| Temperature De-rating |
|
||||||
| Add 0.1 x specified accuracy for each ºC above 28ºC or below 18ºC (above 82.4°F or below 64.4°F) | |||||||
| Safety Specifications | |||||||
| Safety Rating |
|
||||||
| IEC 1010-2-032, 600V CAT III | |||||||
| Mechanical & General Specifications | |||||||
| Size |
|
||||||
| Weight |
|
||||||
| 310 g (11oz) | |||||||
| Warranty |
|
||||||
| Three years | |||||||
| Battery Life |
|
||||||
| Alkaline approximately 150 hours continuous | |||||||
| Automatic low battery indicator | |||||||
| Display Hold |
|
||||||
| Yes | |||||||
Cliquer sur une catégorie pour voir une sélection d'accessoires compatible avec le Fluke 333 Digital 400 Amp AC Clamp Meter.